TECHNICAL SPECIFICATIONS

ModelFront Suction (F4)MVD-22Z/DHN1-F4MVD-28Z/DHN1-F4MVD-36Z/DHN1-F4MVD-45Z/DHN1-F4MVD-56Z/DHN1-F4MVD-71Z/DHN1-F4MVD-80Z/DHN1-F4
Lower Suction (F5)MVD-22Z/DHN1-F5MVD-28Z/DHN1-F5MVD-36Z/DHN1-F5MVD-45Z/DHN1-F5MVD-56Z/DHN1-F5MVD-71Z/DHN1-F5MVD-80Z/DHN1-F5
CodeFront Suction (F4)CL23430CL23431CL23432CL23433CL23434CL23435CL23436
Lower Suction (F5)CL23440CL23441CL23442CL23443CL23444CL23445CL23446
Electrical PowerF, V, Hz1N, 220-240, 50/60
Cooling (1)CapacitykW2,22,83,64,55,67,18
ConsumptionW24242124386262
Heating (2)CapacitykW2,43,2456,389
ConsumptionW23241924416563
FanTypeDC
ModelWZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-3YSK74-4EYSK74-4E
Flow Rate (High / Medium / Low)m3/h530 / 456 / 400569 / 485 / 421624 / 522 / 375660 / 542 / 4401150 / 970 / 8301380 / 1100 / 8701332 / 1212 / 1023
Sound Pressure (High / Medium / Low) (3)dB(A)36 / 33 / 2936 / 33 / 2937 / 34 / 3037 / 34 / 3041 / 35 / 3144 / 39 / 3344 / 39 / 33
Indoor UnitDimensions (W x H x D)NetF4mm1000 x 569 x 2251000 x 569 x 2251200 x 596 x 2251200 x 596 x 2251500 x 596 x 2251500 x 596 x 2251500 x 596 x 225
F5mm1000 x 677 x 2201000 x 677 x 2201200 x 677 x 2201200 x 677 x 2201500 x 677 x 2201500 x 677 x 2201500 x 677 x 220
GrossF4mm1089 x 683 x 3121089 x 683 x 3121289 x 683 x 3121289 x 683 x 3121589 x 683 x 3121589 x 683 x 3121589 x 683 x 312
F5mm1182 x 683 x 3121182 x 683 x 3121382 x 683 x 3121382 x 683 x 3121682 x 683 x 3121682 x 683 x 3121682 x 683 x 312
WeightNetF4Kg29293535404041
F5Kg27,527,5333338,738,741
GrossF4Kg3434434345,545,546,5
F5Kg35,535,541,541,5484850
DrainageConnectionmm25
RefrigerantTypeR410A
Design PressureHighMpa4,4
LowMpa2,6
Refrigerant ConnectionsLiquidmm (in.)6,35 (1/4)6,35 (1/4)6,35 (1/4)6,35 (1/4)9,52 (3/8)9,52 (3/8)9,52 (3/8)
Gasmm (in.)12,7 (1/2)12,7 (1/2)12,7 (1/2)12,7 (1/2)15,9 (5/8)15,9 (5/8)15,9 (5/8)
Electrical Connections (4)Powermm22 x 2.5 + T (L<20m)
Signalmm23 x 0.75 (Shielded)
Remote controlModelRM05
TypeWireless

Notes:

(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(3) Sound level measured in a semi-anechoic chamber at a frontal distance of 1m and a height of 1.5m.

(4) Recommended power wiring for L < 20m, for longer distances it must be calculated.

Characteristics

  • DC Fan Motor
  • 4 LED Display
  • Wide range with front and bottom extraction equipment
  • Wireless remote control included