4-Way Cassette MVD DC

TECHNICAL SPECIFICATIONS

ModelMVD-56Q4/DHN1-DMVD-71Q4/DHN1-DMVD-80Q4/DHN1-DMVD-D90Q4/N1-DMVD-112Q4/DHN1-DMVD-140Q4/DHN1-D
CodeCL23343CL23344CL23325 / CL23345CL23326 / CL23346CL23327 / CL23347CL23328 / CL23348
Electrical PowerF, V, Hz1N, 220-240, 50/60
Cooling (1)CapacitykW5,67,18911,214
ConsumptionW314648757594
Heating (2)CapacitykW6,3891012,515
ConsumptionW314648757594
FanTypeDC
ModelWZDK80-38GWZDK80-38GWZDK80-38GWZDK90-38GWZDK90-38GWZDK90-38G
Flow Rate (High / Medium / Low)m3/h1029 / 857 / 7041200 / 996 / 7481264 / 1055 / 8111596 / 1239 / 10301596 / 1239 / 10301727 / 1426 / 1220
Sound Pressure (High / Medium / Low) (3)dB(A)43 / 38 / 3445 / 39 / 3446 / 40 / 3547 / 41 / 3647 / 41 / 3650 / 45 / 35
UI (Body)Dimensions (W x H x D)Netmm904 x 230 x 840904 x 230 x 840904 x 230 x 840904 x 300 x 840904 x 300 x 840904 x 300 x 840
Grossmm955 x 260 x 955955 x 260 x 955955 x 260 x 955955 x 330 x 955955 x 330 x 955955 x 330 x 955
WeightNetKg24242427,427,430
GrossKg29,529,529,533,233,235,8
PanelModelT-MBQ4-02B1
Dimensions (W x H x D)Netmm950 x 54,5 x 950
Grossmm1035 x 90 x 10351035 x 90 x 10351035 x 90 x 10351035 x 90 x 10351035 x 90 x 10351035 x 90 x 1035
WeightNetKg5
GrossKg8
DrainageConnectionmm32
Drain Height (4)mm750
RefrigerantTypeR410A
Design PressureHighMpa4,4
LowMpa2,6
Refrigerant ConnectionsLiquidmm (in.)9,52 (3/8)9,52 (3/8)9,52 (3/8)9,52 (3/8)9,52 (3/8)9,52 (3/8)
Gasmm (in.)15,9 (5/8)15,9 (5/8)15,9 (5/8)15,9 (5/8)15,9 (5/8)15,9 (5/8)
Electrical Connections (5)Powermm22 x 2.5 + T (L<20m)
Signalmm23 x 0.75 (Shielded)
Remote controlModelRM05
TypeWireless

Notes:

(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(3) Sound level measured in a semi-anechoic chamber at a frontal distance of 1m and a height of 1.4m.

(4) Maximum height from the base of the unit.

(5) Recommended power wiring for L 20m, for longer distances it must be calculated.

Characteristics

  • DC Fan Motor
  • Digital LED Display
  • Outdoor air supply inlet
  • Contribution outlets to adjoining room
  • Condensate pump included
  • Wireless remote control included

Technical documentation

Technical Data Sheet ES 18X18
User Manual ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
Installation Manual ES 18X18 EN 18X18
Technical Manual EN 18X18