MUP-W7 Series

MUP-W7 Series Wall-Mounted Fan Coil Unit

TECHNICAL SPECIFICATIONS

ModelMUP-07-W7MUP-09-W7MUP-12-W7MUP-18-W7
CodeCL04315CL04316CL04317CL04318
RefrigerationCapacity (High / Medium / Low) (*1)kW2,2 / 2,2 / 1,972,64 / 2,48 / 2,063,08 / 2,90 / 2,664,45 / 3,95 / 3,21
Water flowm3/h0,3780,4540,5300,765
Pressure dropkPa23,133,64236,3
Heating50ºCCapacity (High / Medium / Low) (*2)kW3,02 / 2,85 / 2,353,69 / 2,92 / 2,494,34 / 3,77 / 3,356,30 / 5,17 / 4,18
Pressure dropkPa2231,44032,8
70ºCCapacity (High / Medium / Low) (*3)kW4,91 / 4,45 / 3,855,52 / 4,56 / 4,086,69 / 5,88 / 5,499,20 / 8,07 / 6,86
Pressure dropkPa27,534,441,935,1
Air flow (High / Medium / Low)m3/h425 / 410 / 320510 / 427 / 349680 / 550 / 5041.020 / 820 / 670
Heat exchanger water volumeL0,2200,2200,2200,271
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
Consumption (High)W10,714,33337,5
Sound pressure (High / Medium / Low) (*4)dB(A)30 / 26 / 2332 / 28 / 2536 / 32 / 2940 / 36 / 31
Max. operating pressureMPa1,61,61,61,6
Water connectionsinch3/4″3/4″3/4″3/4″
Drain connectionmm20202020
Dimensions (Width x Height x Depth)mm915 × 210 × 290915 × 210 × 290915 × 210 × 2901070 × 210 × 315
Weightkg12121214,8

Notes:

(1) Cooling capacity for each of the 3 air flows and according to conditions: Water inlet/outlet temp. 7/12ºC, Ambient temp. 27ºC DB, 19ºC WB.

(2) Heating capacity for each of the 3 airflows and according to conditions: Water inlet/outlet temp. 50ºC/*, Ambient Temp. 20ºC.

(3) Heating capacity for each of the 3 airflows and according to conditions: Water inlet/outlet temp. 70/60ºC, Ambient Temp. 20ºC.

(4) Sound pressure level measured in a semi-anechoic chamber.

– The design and specifications are subject to change without notice for product improvement.

Characteristics

  • 2-pipe wall-mounted fan coil unit
  • 3-way valve with bypass included
  • Low consumption and silent DC fan motor
  • Automatic blade oscillation
  • Digital Display
  • Remote ON/OFF signal
  • Wireless remote control included
  • Wall remote control with “Follow me” function KJR-29B (Optional)
  • CCM Centralized Control (Optional)

Technical documentation

Technical Data Sheet ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
User and Installation Manual ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
Technical Manual EN 18X18