MUCS-W9 Series

MUCS-W9 Series Cassette Type Fan Coil

TECHNICAL SPECIFICATIONS

ModelMUCS-20-W9MUCS-24-W9MUCS-36-W9
CodeCL04433CL04434CL04435
RefrigerationCapacity (High / Medium / Low) (*1)kW6,12 / 5,45 / 4,67,87 / 7,12 / 6,6711,19 / 8,82 / 7,48
Water flow (High / Medium / Low)m 3 /h1,10 / 0,96 / 0,811,44 / 1,28 / 1,221,96 / 1,53 / 1,28
Pressure drop (High / Medium / Low)kPa21,3 / 21,3 / 12,422,3 / 18,1 / 16,336,6 / 22,7 / 16,4
Heating45ºCCapacity (High / Medium / Low) (*2)kW6,27 / 6,53 / 5,439,16 / 8,54 / 7,910,07 / 10,08 / 8,68
Water flow (High / Medium / Low)m 3 /h1,39 / 1,20 / 1,001,73 / 1,57 / 1,462,35 / 1,86 / 1,59
Pressure drop (High / Medium / Low)kPa30 / 22,7 / 16,328,8 / 24 / 20,749,2 / 31,2 / 23,3
50ºCCapacity (High / Medium / Low) (*3)kW8,62 / 7,49 / 6,2710,92 / 9,84 / 9,1614,92 / 11,73 / 10,07
Water flow (High / Medium / Low)m 3 /h1,10 / 0,96 / 0,811,44 / 1,28 / 1,221,96 / 1,53 / 1,28
Pressure drop (High / Medium / Low)kPa19,1 / 14,8 / 10,620 / 16,2 / 14,734,3 / 21,3 / 15
Air flow (High / Medium / Low)m 3 /h1.229 / 1.020 / 8101.581 / 1.371 / 1.2361.871 / 1.415 / 1.198
Heat exchanger water volumeL0.6771.0151.015
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
ConsumptionW5090124
Sound pressure (High / Medium / Low) (*4)dB(A)44 / 40 / 3448 / 44 / 4149 / 43 / 39
Max. operating pressureMPa1.61.61.6
Fresh air intakemmΦ75Φ75Φ75
Water connectionsinch3/4″3/4″3/4″
Drain connectionmmΦ32Φ32Φ32
DimensionsBody (Width x Height x Depth)mm840 x 230 x 840840 x 300 x 840840 x 300 x 840
Panel (Width x Height x Depth)mm950 x 45 x 950950 x 45 x 950950 x 45 x 950
WeightBodykg232729.5
Panelkg666

Notes:

(1) Cooling capacity for each of the 3 air flows and according to conditions: Water inlet/outlet temp. 7/12ºC, Ambient temp. 27ºC DB, 19ºC WB.
(2) Heating capacity for each of the 3 air flows and according to conditions: Water inlet/outlet temp. 45/40ºC, Ambient temp. 20ºC.
(3) Heating capacity for each of the 3 air flows and according to conditions: Water inlet temp. 50ºC, Ambient temp. 20ºC (for other temperatures see the
technical manual).
(4) Sound pressure level measured in a reverberation chamber, 1m away from the equipment both horizontally and vertically.
– The design and specifications are subject to change without prior notice for product improvement.

Characteristics

  • 2-pipe cassette type fan coil
  • Total 360° design panel
  • Condensate pump
  • DC fan motor with 3 speeds
  • 0-10V input for speed selection
  • Individual control of the louvers (only with RM12F)
  • Inlet for outdoor air supply
  • Outlet for supply to adjoining room
  • Digital display with the possibility of turning it off (only via the
    RM12F control)
  • Remote ON/OFF signal
  • Possibility of modifying the compensation temperature
  • Possibility of connection to CCM centralized control
  • Integrated Modbus (RTU) communication
  • Remote control not included, RM12F recommended (CL97820)

Technical documentation

Technical Data Sheet ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
User and Installation Manual ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
Technical Manual EN 18X18