TECHNICAL SPECIFICATIONS
| Model | MVD-22Q4/DHN1-A3 | MVD-28Q4/DHN1-A3 | MVD-36Q4/DHN1-A3 | MVD-45Q4/DHN1-A3 | |||
|---|---|---|---|---|---|---|---|
| Code | CL23330 / CL23350 | CL23331 / CL23351 | CL23332 / CL23352 | CL23333 / CL23353 | |||
| Electrical Power | F, V, Hz | 1N, 220-240, 50/60 | |||||
| Cooling (1) | Capacity | kW | 2,2 | 2,8 | 3,6 | 4,5 | |
| Consumption | W | 15 | 16 | 21 | 21 | ||
| Heating (2) | Capacity | kW | 2,4 | 3,2 | 4,0 | 5,0 | |
| Consumption | W | 13 | 13 | 18 | 18 | ||
| Fan | Type | DC | |||||
| Model | WZDK37-38G | WZDK37-38G | WZDK37-38G | WZDK37-38G | |||
| Flow Rate (High / Medium / Low) | m3/h | 526 / 449 / 364 | 576 / 503 / 405 | 604 / 516 / 400 | 604 / 516 / 400 | ||
| Sound Pressure (High / Medium / Low) (3) | dB(A) | 34 / 32 / 22 | 34 / 32 / 22 | 40 / 34 / 27 | 40 / 34 / 27 | ||
| Indoor Unit | Dimensions (W x H x D) | Net | mm | 570 x 260 x 570 | 570 x 260 x 570 | 570 x 260 x 570 | 570 x 260 x 570 |
| Gross | mm | 675 x 285 x 675 | 675 x 285 x 675 | 675 x 285 x 675 | 675 x 285 x 675 | ||
| Weight | Net | Kg | 16 | 16 | 17,5 | 17,5 | |
| Gross | Kg | 22 | 22 | 23,5 | 23,5 | ||
| Panel | Model | T-MBQ4-03B1 | |||||
| Dimensions (W x H x D) | Net (W x H x D) | mm | 647 x 50 x 647 | 647 x 50 x 647 | 647 x 50 x 647 | 647 x 50 x 647 | |
| Gross (W x H x D) | mm | 715 x 113 x 715 | 715 x 113 x 715 | 715 x 113 x 715 | 715 x 113 x 715 | ||
| Weight | Net | Kg | 3 | ||||
| Gross | Kg | 5 | |||||
| Drainage | Connection | mm | 25 | ||||
| Drain Height (4) | mm | 600 | |||||
| Refrigerant | Type | R410A | |||||
| Design Pressure | High | Mpa | 4,4 | ||||
| Low | Mpa | 2,6 | |||||
| Refrigerant Connections | Liquid | mm (in.) | 6,35 (1/4) | 6,35 (1/4) | 6,35 (1/4) | 6,35 (1/4) | |
| Gas | mm (in.) | 12,7 (1/2) | 12,7 (1/2) | 12,7 (1/2) | 12,7 (1/2) | ||
| Electrical Connections (5) | Power | mm2 | 2 x 2.5 + T (L<20m) | ||||
| Signal | mm2 | 3 x 0.75 (Shielded) | |||||
| Remote control | Model | RM05 | |||||
| Type | Wireless | ||||||
Notes:
(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.
(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.
(3) Sound level measured in a semi-anechoic chamber at a frontal distance of 1m and a height of 1.4m.
(4) Maximum height from the base of the unit.
(5) Recommended power wiring for L 20m, for longer distances it must be calculated.