1-Way Cassette MVD D4+

TECHNICAL SPECIFICATIONS

ModelMVD-D28Q1/N1-DMVD-D36Q1/N1-DMVD-D45Q1/N1-CMVD-D56Q1/N1-C
CodeCL23150CL23151CL23152CL23153
Electrical PowerF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW2,83,64,55,6
Power ConsumptionW41418085
IntensityA0,250,250,370,39
Heating (2)CapacitykW3,2456,3
Power ConsumptionW41418085
IntensityA0,250,250,370,39
FanBrandWellingWellingWellingWelling
TypeACACACAC
ModelRPS12NRPS12NYSK-55-4YSK-55-4
Flow rate (S. High / High / Medium / Low)m³/h573 / 456 / 315573 / 456 / 315704 / 630 / 503860 / 810 / 702
Sound Level (High / Medium / Low) (3)dB(A)39 / 37 / 3440 / 38 / 3441 / 39 / 3542 / 40 / 36
Indoor UnitDimensionsNet (W x H x D)mm1054 x 169 x 4251054 x 169 x 4251147 x 200 x 6401147 x 200 x 640
Gross (W x H x D)mm1155 x 255 x 4901155 x 255 x 4901380 x 265 x 7751380 x 265 x 775
WeightNetKg131331,531,5
GrossKg16,516,537,237,2
PanelModelMBQ1-02DMBQ1-02DT-MBQ1-03AT-MBQ1-03A
DimensionsNet (W x H x D)mm1180 x 36,5 x 4651180 x 36,5 x 4651425 x 10 x 7551425 x 10 x 755
Gross (W x H x D)mm1232 x 107 x 5171232 x 107 x 5171500 x 110 x 8701500 x 110 x 870
WeightNetKg3,53,599
GrossKg5,25,21212
DrainageConnectionmm?25?25?25?25
Drain Height (4)mm750750750750
RefrigerantTypeR410AR410AR410AR410A
Design PressureHighMpa4,44,44,44,4
LowMpa2,62,62,62,6
Refrigerant ConnectionsLiquidmm (“)6,35 (1/4)6,35 (1/4)6,35 (1/4)9,52 (3/8)
Gasmm (“)12,7 (1/2)12,7 (1/2)12,7 (1/2)15,9 (5/8)
Electrical Connections (5)Powermm22 x 2.5 + T (L<20m)2 x 2.5 + T (L<20m)2 x 2.5 + T (L<20m)2 x 2.5 + T (L<20m)
Signalmm23 x 0.75 (Shielded)3 x 0.75 (Shielded)3 x 0.75 (Shielded)3 x 0.75 (Shielded)
Remote controlModelRM05RM05RM05RM05
TypeWirelessWirelessWirelessWireless

Notes:

(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(3) Sound level measured in an anechoic chamber at a frontal distance of 1m and a height of 1.4m.

(4) Maximum height from the base of the unit.

(5) Recommended power wiring for L 20m, for longer distances it must be calculated.

Characteristics

  • Digital LED Display (models 28 and 36)
  • 4 LED Display (models 45 and 56)
  • Outdoor air supply inlet
  • Condensate pump included
  • Wireless remote control included

Technical documentation

User Manual EN EN
Installation Manual EN
Technical Manual EN