MUCO-H6 Series Column Type Air Conditioner
TECHNICAL SPECIFICATIONS
| Model | MUCO-48-H6T | MUCO-60-H6T | |||
|---|---|---|---|---|---|
| Code | CL20390 | CL20391 | |||
| Refrigeration | Nominal capacity | kW | 12,31 | 15,00 | |
| Nominal consumption (max) | kW | 4,90 (6,40) | 6,00 (7,00) | ||
| EER | W/W | 2,51 | 2,50 | ||
| Heating | Nominal capacity | kW | 12,31 | 17,50 | |
| Nominal consumption (max) | kW | 4,40 (5,80) | 5,85 (8,00) | ||
| COP | W/W | 2,80 | 2,99 | ||
| Indoor Unit | Air flow (Super High / High / Medium / Low) | m3/h | 1.950 / 1.900 / 1.700 / 1.530 | 2.000 / 1.900 / 1.700 / 1.530 | |
| Sound Pressure (Super High / High / Medium / Low) | dB(A) | 55 / 53 / 49 / 45 | 52 / 50 / 46 / 44 | ||
| Sound Power (Super High / High / Medium / Low) | dB(A) | 65 / 63 / 59 / 55 | 62 / 60 / 56 / 54 | ||
| Auxiliary electric resistance (1*) | Power | kW | 2,50 | 2,50 | |
| Electrical Supply (2*) | V-Hz-F | 380-415V~ 50Hz, 3F | 380-415V~ 50Hz, 3F | ||
| Power cable (2*) | mm2 | 4 x 2,5 + T | 4 x 2,5 + T | ||
| Dimensions (Width x Height x Depth) | mm | 518 x 1870 x 395 | 518 x 1870 x 395 | ||
| Weight | kg | 58 | 61 | ||
| Outdoor Unit | Air flow (High) | m3/h | 3.600 | 3.600 | |
| Fans | Type | Axial | Axial | ||
| Quantity | 1 | 2 | |||
| Sound Pressure (High) | dB(A) | 59 | 62,0 | ||
| Sound Power (High) | dB(A) | 69 | 72 | ||
| Compressor (Brand / Model) | SANYO / C-SBP160H38C | SANYO / C-SBP185H38A | |||
| Electrical Power | V-Hz-F | 380-415V~ 50Hz, 3F | 380-415V~ 50Hz, 3F | ||
| Power cable | mm2 | 4 x 6 + T | 4 x 6 + T | ||
| Dimensions (Width x Height x Depth) | mm | 1018 x 840 x 412 | 1032 x 1250 x 412 | ||
| Weight | kg | 90 | 114 | ||
| Set | Communication cable (3*) | 5-wire cable (length) | m | Included (5m) | Included (5m) |
| 4-wire cable (length) | m | Included (5m) | Included (5m) | ||
| Refrigerant | Type | R410A | R410A | ||
| Load | Kg | 3,1 | 4,3 | ||
| Precharge up to | m | 5 | 5 | ||
| Additional charge (from 5m) | g/m | 100 | 100 | ||
| Design pressure | MPa | 4,3 / 2,5 | 4,3 / 2,5 | ||
| Refrigerant pipes | Liquid / Gas | mm (inch) | 12,7 / 19 (1/2 “/ 3/4”) | 12,7 / 19 (1/2 “/ 3/4”) | |
| Maximum length | m | 30 | 30 | ||
| Maximum height difference | m | 20 | 20 | ||
| Included wireless remote control model | YB1F2 | YB1F2 | |||
| Operating temp. | Indoor (Cooling / Heating) | ºC | 16 to 30 / 16 to 30 | 16 to 30 / 16 to 30 | |
| Outdoor (Cooling / Heating) | ºC | 18 to 43 / -7 to 24 | 18 to 43 / -7 to 24 | ||
Notes:
(1*) The auxiliary resistance only works if it is manually activated, it has not been taken into account for the indicated consumption data, if it is activated in heating mode the consumption will be 2.5kW higher
(2*) In case of not powering the indoor unit through the outdoor unit
(3*) If the indoor unit is powered through the outdoor unit, an additional 4 x 2.5 + T cable will be necessary (not included)
– The design and specifications are subject to change without notice for product improvement.
– The sound level values correspond to values obtained in an anechoic chamber.