The Mini MVD V4+ system, consisting of 8 to 45kW units, allows the connection of up to 14 indoor units to the same outdoor unit, with a maximum pipe length of up to 250m.
Super DC Inverter
All equipment in the range incorporates a DC Inverter compressor and fan motor, thus improving system performance at medium frequencies and ensuring more sensitive and effective control.
Wide Range of Capacities
The new Mini MVD V4+ system has units with a wide range of capacities, from 8kW to 45kW, which offers the possibility of connecting from 4 to 14 indoor units respectively.
Auto Addressing
The outdoor unit can automatically assign addresses to the indoor units.
The wireless controls and the KJR-29B wiring can also configure, consult and modify the addresses of the indoor units.
Simplified Communication Connection
The installation of the communication wiring is simpler since, if it is necessary to install a centralized control, it is not necessary to wire a second communication bus between the indoor units and the centralized control. You can connect the centralized control directly to the outdoor unit and perform automatic addressing so that the control detects all the indoor units connected to that outdoor unit, later we can manually modify the addresses with the individual control of each indoor unit.
Maximum Pipe Length of up to 250m
The Mini MVD V4+ system supports a maximum pipe length of up to 120m (20, 22.4 and 26kW capacities) and up to 250m (40 and 45kW capacities) and a height difference of up to 30m.
Wide Operating Range
The Mini MVD V4+ system can operate in extreme temperature conditions, in heating mode up to a temperature of -15ºC and in cooling mode up to 48ºC.
Full Compatibility
The Mini MVD V4+ system is compatible with all MVD indoor units.
TECHNICAL SPECIFICATIONS
| Model | MVD-V80W/DN1 | MVD-V105W/DN1 | MVD-V120W/DN1 | MVD-V140W/DN1 | MVD-V160W/DN1(B) | ||
|---|---|---|---|---|---|---|---|
| Code | CL23260 | CL23261 | CL23262 | CL23263 | CL23264 | ||
| Electrical Power | 1N-, 230V, 50Hz | 1N-, 230V, 50Hz | 1N-, 230V, 50Hz | 1N-, 230V, 50Hz | 1N-, 230V, 50Hz | ||
| Cooling (1) | Capacity | kW | 7.2 (1.5 ~ 8) | 9.0 (2 ~ 10) | 12,30 | 14,00 | 15,50 |
| Power Consumption | kW | 1.82 (0.71 ~ 1.86) | 2.3 (0.89 ~ 2.59) | 3,25 | 3,95 | 4,52 | |
| EER / SEER (7) | 3,95 / 5,30 | 3,91 / 5,60 | 3,78 / 5,67 | 3,54 / 5,92 | 3,43 / 6,05 | ||
| Heating (2) | Capacity | kW | 7,2 (1,6 – 8,4) | 9,0 (2,1 – 10,5) | 13,20 | 15,40 | 17,00 |
| Power Consumption | kW | 1,76 (0,83 – 2,11) | 2,27 (1,06 – 2,77) | 3,47 | 4,16 | 4,77 | |
| COP / SCOP (7) | 4,09 / 3,90 | 3,97 / 3,80 | 3,8 / 3,90 | 3,7 / 3,86 | 3,56 / 3,64 | ||
| Nominal Intensity | A | 18,50 | 22,80 | 24,40 | 29,80 | 30,00 | |
| Connectivity | Connectable Cap. | % | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 |
| No. max indoor | 4 | 5 | 6 | 6 | 7 | ||
| Compressor | Brand | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | |
| Type | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | ||
| Model | TNB220FLHMC | TNB220FLHMC | TNB306FPGMC | TNB306FPGMC | LNB42FSCMC | ||
| Fan | Type | DC | DC | DC | DC | DC | |
| Quantity | 1 | 1 | 2 | 2 | 2 | ||
| Model | WZDK170-38G-1 | WZDK170-38G-1 | WZDK100-38G | WZDK100-38G | WZDK100-38G | ||
| Flow | m³/h | 5.500 | 5.500 | 6.000 | 6.000 | 6.000 | |
| Consumption | W | 195 | 195 | 100 x2 | 100 x2 | 100 x2 | |
| Sound Pressure (3) | dB(A) | 56 | 57 | 57 | 57 | 57 | |
| Dimensions | Net (W x H x D) | mm | 990 x 966 x 336 | 990 x 966 x 336 | 900 x 1327 x 320 | 900 x 1327 x 320 | 900 x 1327 x 320 |
| Gross (W x H x D) | mm | 1120 x 1015 x 435 | 1120 x 1015 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | |
| Weight | Net | Kg | 75,5 | 75,5 | 95,0 | 95,0 | 100,0 |
| Gross | Kg | 85,5 | 85,5 | 106,0 | 106,0 | 111,0 | |
| Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | |
| Quantity | kg / TCO2eq | 2,95 / 6,16 | 2,95 / 6,16 | 3,3 / 6,89 | 3,9 / 8,14 | 3,9 / 8,14 | |
| Refrigerant Distances (4) | Max. Vertical | m | 20 | 20 | 20 | 20 | 20 |
| Total | m | 100 | 100 | 100 | 100 | 100 | |
| Refrigerant Connections (5) | Liquid | mm | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) |
| Gas | mm | 15.9 (5/8″) | 15.9 (5/8″) | 15.9 (5/8″) | 15.9 (5/8″) | 19.1 (3/4″) | |
| Electrical Connections (6) | Power Wiring / ICP | mm2 / A | 2 x 6 + T / 25 | 2 x 6 + T / 30 | 2 x 6 + T / 30 | 2 x 10 + T / 40 | 2 x 10 + T / 40 |
| Signal | mm2 | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | |
| Operating Temperature Range | Refrigeration | ºC | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 |
| Heating | ºC | -15 to 27 | -15 to 27 | -15 to 27 | -15 to 27 | -15 to 27 | |
| Model | MVD-V120W/DRN1 | MVD-V140W/DRN1 | MVD-V160W/DRN1 | MVD-V180W/DRN1 | MVD-V200W/DRN1 | MVD-V224W/DRN1 | MVD-V260W/DRN1 | ||
|---|---|---|---|---|---|---|---|---|---|
| Code | CL23265 | CL23266 | CL23267 | CL23268 | CL23269 | CL23270 | CL23271 | ||
| Electrical Power | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | ||
| Cooling (1) | Capacity | kW | 12,30 | 14,00 | 15,50 | 17,50 | 20,00 | 22,40 | 26,00 |
| Power Consumption | kW | 3,25 | 3,95 | 4,52 | 5,30 | 6,10 | 6,80 | 7,60 | |
| EER / SEER (7) | 3,78 / 5,67 | 3,54 / 5,92 | 3,43 / 6,05 | 3,30 / 5,13 | 3,28 / 5,58 | 3,29 / 6,07 | 3,42 / 5,43 | ||
| Heating (2) | Capacity | kW | 13,20 | 15,40 | 17,00 | 19,00 | 22,00 | 24,50 | 28,50 |
| Power Consumption | kW | 3,47 | 4,16 | 4,77 | 5,00 | 6,10 | 5,90 | 6,80 | |
| COP / SCOP (7) | 3,80 / 3,90 | 3,70 / 3,86 | 3,56 / 3,64 | 3,80 / 3,86 | 3,61 / 3,64 | 4,15 / 3,74 | 4,19 / 3,76 | ||
| Nominal Intensity | A | 10,00 | 11,00 | 12,00 | 12,50 | 14,50 | 16,20 | 18,70 | |
| Connectivity | Connectable Cap. | % | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 | 45 – 130 |
| No. max indoor | 6 | 6 | 7 | 9 | 10 | 11 | 12 | ||
| Compressor | Brand | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | Mitsubishi Electric | |
| Type | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | DC Inverter – Rotary | ||
| Model | TNB306FPNMC | TNB306FPNMC | LNB42FSAMC | LNB42FSAMC | LNB42FSAMC | LNB53FCAMC | LNB53FCAMC | ||
| Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||
| Fan | Type | DC | DC | DC | DC | DC | DC | DC | |
| Quantity | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||
| Model | WZDK100-38G | WZDK100-38G | WZDK100-38G | WZDK100-38G | WZDK170-38-G-1 | WZDK170-38-G-1 | WZDK170-38-G-1 | ||
| Flow | m³/h | 6.000 | 6.000 | 6.000 | 6.800 | 10.999 | 10.494 | 10.494 | |
| Sound Pressure (3) | dB(A) | 57 | 57 | 57 | 59 | 59 | 59 | 60 | |
| Dimensions | Net (W x H x D) | mm | 900 x 1327 x 320 | 900 x 1327 x 320 | 900 x 1327 x 320 | 900 x 1327 x 320 | 1120 x 1558 x 414 | 1120 x 1558 x 414 | 1120 x 1558 x 414 |
| Gross (W x H x D) | mm | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1270 x 1720 x 565 | 1270 x 1720 x 565 | 1270 x 1720 x 565 | |
| Weight | Net | Kg | 95,0 | 95,0 | 102,0 | 107,0 | 137,0 | 146,5 | 147,0 |
| Gross | Kg | 103,0 | 103,0 | 113,0 | 118,0 | 153,0 | 165,5 | 163,0 | |
| Refrigerant | Type / GWP | R410A | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | |
| Quantity | kg / TCO2eq | 3,3 / 6,89 | 3,9 / 8,14 | 3,9 / 8,14 | 4,5 / 9,4 | 4,8 / 10,02 | 6,2 / 12,95 | 6,2 / 12,95 | |
| Refrigerant Distances (4) | Max. Vertical | m | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
| Total | m | 100 | 100 | 100 | 100 | 120 | 120 | 120 | |
| Refrigerant Connections (5) | Liquid | mm | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) | 9.52 (3/8″) |
| Gas | mm | 15.9 (5/8″) | 15.9 (5/8″) | 19.1 (3/4″) | 19.1 (3/4″) | 19.1 (3/4″) | 19.1 (3/4″) | 22.2 (7/8″) | |
| Electrical Connections (6) | Power Wiring / ICP | mm2 / A | 4 x 4 + T / 25 | 4 x 4 + T / 25 | 4 x 4 + T / 25 | 4 x 4 + T / 25 | 4 x 6 + T / 30 | 4 x 6 + T / 30 | 4 x 10 + T / 40 |
| Signal | mm2 | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | |
| Operating Temperature Range | Refrigeration | ºC | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 | -15 to 43 |
| Heating | ºC | -15 to 27 | -15 to 27 | -15 to 27 | -15 to 27 | -15 to 24 | -15 to 24 | -15 to 24 | |
| Model | MVD-V400W/DRN1 | MVD-V450W/DRN1 | ||
|---|---|---|---|---|
| Code | CL23272 | CL23273 | ||
| Electrical Power | F, V, Hz | 3N-, 400V, 50Hz | 3N-, 400V, 50Hz | |
| Cooling (1) | Capacity | kW | 40,00 | 45,00 |
| Power Consumption | kW | 11,90 | 13,60 | |
| EER / SEER (7) | 3,35 / 5,08 | 3,32 / 5,03 | ||
| Heating (2) | Capacity | kW | 45,00 | 50,00 |
| Power Consumption | kW | 11,10 | 12,70 | |
| COP / SCOP (7) | 4,05 / 3,51 | 3,93 / 3,45 | ||
| Nominal Intensity | A | 33,00 | 44,00 | |
| Connectivity | Connectable Capacity | % | 45 – 130 | 45 – 130 |
| Max. No. of Indoor Units | 14 | 14 | ||
| Compressor | Brand | Mitsubishi Electric | Mitsubishi Electric | |
| Type | DC Inverter – Rotary | DC Inverter – Rotary | ||
| Model | LNB42FSAMC | LNB53FCAMC | ||
| Capacity | kW | 2 | 2 | |
| Fan | Type | DC | DC | |
| Quantity | 2 | 2 | ||
| Model | WZDK560-38G(B) | WZDK560-38G(B) | ||
| Flow | m3/h | 16.575 | 16.575 | |
| Sound Pressure (3) | dB | 62 | 62 | |
| Dimensions | Net (Width x Height x Depth) | mm | 1360 x 1650 x 540 | 1460 x 1650 x 540 |
| Gross (Width x Height x Depth) | mm | 1450 x 1785 x560 | 1550 x 1785 x560 | |
| Weight | Net | Kg | 240 | 275 |
| Gross | Kg | 260 | 290 | |
| Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | |
| Quantity | kg / TCO2eq | 9,0 / 18,79 | 12,0 / 25,06 | |
| Refrigerant Distances (4) | Max. Vertical | m | 20 | 20 |
| Total | m | 250 | 250 | |
| Refrigerant Connections (5) | Liquid Line | mm (in.) | 12.7 (1/2″) | 12.7 (1/2″) |
| Gas Line | mm (in.) | 22.2 (7/8″) | 25.4 (1″) | |
| Electrical Connections (6) | Power Wiring / ICP | mm2 / A | 4 x 25 + T / 70 | 4 x 35 + T / 90 |
| Signal Wiring | mm2 | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | |
| Operating Temperature Range | Refrigeration | ºC | -5 to 43 | -5 to 43 |
| Heating | ºC | -15 to 24 | -15 to 24 | |
Notes:
(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, 24ºC WB, for a pipe length of 7.5 m and height difference 0 m.
(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, 6ºC WB, for a pipe length of 7.5 m and height difference 0 m.
(3) Sound level measured in a semi-anechoic chamber at a distance of 1m from the front and 1.2m in height (1.3m for models 200 to 260).
(4) Refrigerant distances when the outdoor unit is installed higher than the indoor units. Otherwise, the maximum vertical distance can reach 30m.
(5) Refrigerant pipe diameters indicated are for the service valves, this does not mean that the pipe must be of this diameter. Otherwise, the maximum vertical distance can reach 30m.
(6) Recommended power wiring for L 20m, for longer distances it must be calculated.
(7) Data measured under EUROVENT EN 14825 conditions, at 100% simultaneity