Maxi MVD V5X (2 pipes)
The Super DC Inverter modular system Maxi MVD V5X (2 pipes) consists of 8 basic modules that can be combined with each other, allowing a maximum power of up to 246 kW, which is the highest on the market, and supports a maximum pipe length of up to 1000 m.
Super DC Inverter
All compressors and fan motors are DC Inverter, which improves the system’s performance at medium frequencies and ensures more sensitive and effective control.
Maximum Market Capacity (up to 246kW)
With the 8 basic modules (8, 10, 12, 14, 16, 18, 20 and 22HP) that can be combined with each other (max. 4 units), they form the largest capacity on the market with 88HP (246kW).
Maximum Efficiency with a SEER of up to 7.3
Thanks to the new design of the 3-row heat exchanger, the exchange surface has been increased by 21%.
(SEER: Seasonal Energy Efficiency Ratio)
Auto Addressing
The outdoor unit can automatically assign addresses to the indoor units.
The wireless controls and the KJR-29B wiring can also configure, consult and modify the addresses of the indoor units.
Simplified Communication Connection
The installation of the communication wiring is simpler since, if it is necessary to install a centralized control, it is not necessary to wire a second communication bus between the indoor units and the centralized control. You can connect the centralized control directly to the outdoor unit and perform automatic addressing so that the control detects all the indoor units connected to that outdoor unit, later we can manually modify the addresses with the individual control of each indoor unit.
Precise Temperature Control
Thanks to the advantages of MVD systems, maximum performance and comfort can be quickly achieved, shortening heating and cooling times.
Low Noise Level
The optimal fan design and the new design of the air outlet grille and deflector allow for greater air flow and lower noise levels during operation.
Night Mode
Possibility of establishing night schedules in which to reduce the noise level. There are four different levels of reduction.
Fast Defrosts
Technology to reduce defrost time.
Rotation & Backup
In a modular system, the rotation function allows any unit to start as master, which allows all compressors to work the same amount of hours.
Maximum Pipe Length of up to 1000m
The Maxi MVD V5X system supports a maximum pipe length of 1000m and a height difference of 90m or even 110m in the case that the outdoor unit is installed lower than the indoor units.
High Static Pressure
The static pressure of the fan can be increased to 40Pa simply by configuring a micro-switch, in this way the air discharge of the outdoor unit can be conducted.
Full Compatibility
The Maxi MVD V5X system is compatible with all MVD indoor units.
TECHNICAL SPECIFICATIONS
| Model | MVD-V5X252W/V2GN1 | MVD-V5X280W/V2GN1 | MVD-V5X335W/V2GN1 | MVD-V5X400W/V2GN1 | |||
|---|---|---|---|---|---|---|---|
| Code | CL23300 | CL23301 | CL23302 | CL23303 | |||
| Electrical Power | F, V, Hz | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | ||
| Cooling (1) | Capacity | kW | 25,2 | 28 | 33,5 | 40 | |
| Consumption (7) | kW | 6,25 | 7,49 | 8,91 | 11,66 | ||
| EER (7) | 4,03 | 3,74 | 3,76 | 3,43 | |||
| Heating (2) | Capacity | kW | 27 | 31,5 | 37,5 | 40 | |
| Consumption (7) | kW | 5,3 | 6,89 | 8,91 | 9,83 | ||
| COP (7) | 5,09 | 4,57 | 4,21 | 4,07 | |||
| Nominal Intensity | A | 20,0 | 21,0 | 23,0 | 27,3 | ||
| Connectivity | Connectable Cap. | % | 50 – 130 | 50 – 130 | 50 – 130 | 50 – 130 | |
| No. max indoor | 13 | 16 | 20 | 23 | |||
| Compressor | Brand | Hitachi | Hitachi | Hitachi | Hitachi | ||
| Type | Scroll DC Inverter | Scroll DC Inverter | Scroll DC Inverter | Scroll DC Inverter | |||
| Quantity | 1 | 1 | 1 | 2 | |||
| Model No. 1 | E655DHD-65D2YG | E655DHD-65D2YG | E705DHD-72D2YG | E405DHD-42D2YG | |||
| Model No. 2 | — | — | — | E405DHD-42D2YG | |||
| Fan | Type | DC | DC | DC | DC | ||
| Quantity | 1 | 1 | 1 | 2 | |||
| Flow | m³/h | 12.000 | 12.000 | 12.000 | 14.000 | ||
| Static Pressure | Standard | Pa | 0 – 20 | 0 – 20 | 0 – 20 | 0 – 20 | |
| Configurable | Pa | 20 – 40 | 20 – 40 | 20 – 40 | 20 – 40 | ||
| Sound Pressure (3) | dB | 58 | 59 | 60 | 62 | ||
| Dimensions | Net (W x H x D) | mm | 990 x 1635 x 790 | 990 x 1635 x 790 | 990 x 1635 x 790 | 1340 x 1635 x 790 | |
| Gross (W x H x D) | mm | 1055 x 1805 x 855 | 1055 x 1805 x 855 | 1055 x 1805 x 855 | 1405 x 1805 x 855 | ||
| Weight | Net | Kg | 219 | 219 | 237 | 297 | |
| Gross | Kg | 234 | 234 | 252 | 315 | ||
| Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | ||
| Quantity | kg / TCO2eq | 9 / 18,79 | 9 / 18,79 | 11 / 22,97 | 13 / 27,14 | ||
| Refrigerant Distances | Max. Vertical | Outdoor above (4) | m | 90 | 90 | 90 | 90 |
| Outdoor below | m | 110 | 110 | 110 | 110 | ||
| Total | m | 1.000 | 1.000 | 1.000 | 1.000 | ||
| Refrigerant Connections (5) | Liquid | mm | 12.7 (1/2″) | 12.7 (1/2″) | 15.9 (5/8″) | 15.9 (5/8″) | |
| Gas | mm | 25.4 (1″) | 25.4 (1″) | 28.6 (1 1/8″) | 31.8 (1 1/4″) | ||
| Oil balance | mm | 6.35 (1/4″) | 6.35 (1/4″) | 6.35 (1/4″) | 6.35 (1/4″) | ||
| Electrical Connections (6) | Power / ICP | mm2 / A | 4 x 6 + T / 25 | 4 x 6 + T / 25 | 4 x 6 + T / 25 | 4 x 10 + T / 30 | |
| Signal | mm2 | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | ||
| Operating Temperature Range | Refrigeration | ºC | -5 to 43 | -5 to 43 | -5 to 43 | -5 to 43 | |
| Heating | ºC | -20 to 24 | -20 to 24 | -20 to 24 | -20 to 24 | ||
| Model | MVD-V5X450W/V2GN1 | MVD-V5X500W/V2GN1 | MVD-V5X560W/V2GN1 | MVD-V5X615W/V2GN1 | |||
|---|---|---|---|---|---|---|---|
| Code | CL23304 | CL23305 | CL23306 | CL23307 | |||
| Electrical Power | F, V, Hz | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | ||
| Cooling (1) | Capacity | kW | 45 | 50 | 56 | 61,5 | |
| Consumption (7) | kW | 13,64 | 14,71 | 16,47 | 19,84 | ||
| EER (7) | 3,30 | 3,40 | 3,40 | 3,10 | |||
| Heating (2) | Capacity | kW | 45 | 50 | 56 | 61,5 | |
| Consumption (7) | kW | 11,69 | 12,50 | 14,00 | 16,18 | ||
| COP (7) | 3,85 | 4,00 | 4,00 | 3,80 | |||
| Nominal Intensity | A | 29,9 | 34,4 | 41,2 | 44,9 | ||
| Connectivity | Connectable Cap. | % | 50 – 130 | 50 – 130 | 50 – 130 | 50 – 130 | |
| No. max indoor | 26 | 29 | 33 | 36 | |||
| Compressor | Brand | Hitachi | Hitachi | Hitachi | Hitachi | ||
| Type | Scroll DC Inverter | Scroll DC Inverter | Scroll DC Inverter | Scroll DC Inverter | |||
| Quantity | 2 | 2 | 2 | 2 | |||
| Model No. 1 | E405DHD-42D2YG | E405DHD-36D2YG | E705DHD-72D2YG | E705DHD-72D2YG | |||
| Model No. 2 | E405DHD-42D2YG | E705DHD-72D2YG | E705DHD-72D2YG | E705DHD-72D2YG | |||
| Fan | Type | DC | DC | DC | DC | ||
| Quantity | 2 | 2 | 2 | 2 | |||
| Flow | m³/h | 14.000 | 16.000 | 16.000 | 16.000 | ||
| Static Pressure | Standard | Pa | 0 – 20 | 0 – 20 | 0 – 20 | 0 – 20 | |
| Configurable | Pa | 20 – 40 | 20 – 40 | 20 – 40 | 20 – 40 | ||
| Sound Pressure (3) | dB | 62 | 63 | 63 | 63 | ||
| Dimensions | Net (W x H x D) | mm | 1340 x 1635 x 790 | 1340 x 1635 x 790 | 1340 x 1635 x 790 | 1340 x 1635 x 790 | |
| Gross (W x H x D) | mm | 1405 x 1805 x 855 | 1405 x 1805 x 855 | 1405 x 1805 x 855 | 1405 x 1805 x 855 | ||
| Weight | Net | Kg | 297 | 305 | 340 | 340 | |
| Gross | Kg | 315 | 323 | 358 | 358 | ||
| Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | ||
| Quantity | kg / TCO2eq | 13 / 27,14 | 13 / 27,14 | 16 / 33,41 | 16 / 33,41 | ||
| Refrigerant Distances | Max. Vertical | Outdoor above (4) | m | 90 | 90 | 90 | 90 |
| Outdoor below | m | 110 | 110 | 110 | 110 | ||
| Total | m | 1.000 | 1.000 | 1.000 | 1.000 | ||
| Refrigerant Connections (5) | Liquid | mm | 15.9 (5/8″) | 19.1 (3/4″) | 19.1 (3/4″) | 19.1 (3/4″) | |
| Gas | mm | 31.8 (1 1/4″) | 31.8 (1 1/4″) | 31.8 (1 1/4″) | 31.8 (1 1/4″) | ||
| Oil balance | mm | 6.35 (1/4″) | 6.35 (1/4″) | 6.35 (1/4″) | 6.35 (1/4″) | ||
| Electrical Connections (6) | Power | mm2 | 4 x 10 + T / 35 | 4 x 16 + T / 40 | 4 x 16 + T / 50 | 4 x 16 + T / 50 | |
| Signal | mm2 | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | 3 x 0.75 (Shielded) | ||
| Operating Temperature Range | Refrigeration | ºC | -5 to 43 | -5 to 43 | -5 to 43 | -5 to 43 | |
| Heating | ºC | -20 to 24 | -20 to 24 | -20 to 24 | -20 to 24 | ||
Notes:
(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, 24ºC WB, for a pipe length of 7.5 m and height difference 0 m.
(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, 6ºC WB, for a pipe length of 7.5 m and height difference 0 m.
(3) Sound values measured in a semi-anechoic chamber at 1m frontal distance and 1.3m height.
(4) For height differences greater than 20m, it is recommended to make an oil trap in the gas pipe, every 10m.
(5) Indicated refrigerant pipe diameters are those of the service valves, this does not mean that the pipe to be installed is of that diameter. Oil balance pipe, only necessary when 2 or more modules are connected.
(6) Recommended power wiring for L 20m, for longer distances it must be calculated.
(7) Data measured in EUROVENT EN 14825 conditions, at 100% simultaneity with duct-type indoor units.