MUEN-HG Series

Digital Scroll Modular Chillers MUEN-HG Series

Copeland Digital Scroll Compressor

In traditional air-cooling systems, output capacity is controlled by turning the compressor on/off. The precision of the control mode is not very good, and the compressor starts and stops frequently, which is not good for its lifespan.

The air-cooled Digital Scroll system breaks with the traditional design, designed with a parallel connection of a Digital Scroll compressor and one (or two) fixed Scroll compressors. The system can achieve a linear adjustment of its capacity from 0.5% to 100%, making the range one of the widest in the industry. When the system is operating at partial load, the cooling or heating power can be precisely adjusted.

Modular System

Modular design allows up to 16 units to operate together, forming a unit of up to 1024kW.

Easy Connection

Easy connection between the master unit and the slave units. All units can be connected via a wired remote control (included with each unit), using a shielded three-pole cable.

Safeguard Function

If the unit gives an error code (E*):

– If it is the master unit, all units stop (one of the slaves can be configured as master to leave the system in service temporarily).

– If it is a slave unit, only that unit stops.

If the unit gives a protection code (P*), that unit stops but the rest continue to run, regardless of whether it is the master or not (except codes PE and P9).

New Heat Exchangers

More reliable system thanks to the new heat exchangers. The 30kW modules incorporate a concentric tube (double tube) heat exchanger, while the 65 kW modules have a shell and tube heat exchanger.

Verification Function

From the display on the unit’s electronic board, different operating parameters can be checked in real time.

Built-in Wired Remote Control

All equipment in the series incorporates a control that allows you to adjust all operating parameters.

Silent Operation

Optimized fan design to minimize noise level.

TECHNICAL SPECIFICATIONS

ModelMUEN-30-HGMUEN-65-HG
CodeCL25604CL25605
Electrical PowerF, V, Hz3N-, 400, 503N-, 400, 50
Cooling (1)CapacitykW3065
Power ConsumptionkW1020,4
IntensityA16,336,5
Max. IntensityA2454,5
Heating (2)CapacitykW3269
Power ConsumptionkW9,821,5
IntensityA1637,2
Max. IntensityA2454,5
CompressorsBrandCopelandCopeland
TypeScrollScroll
Digital ScrollModelZPD67KCE-TFD-532ZPD72KCE-TFD-433
Quantity11
CapacitykW16,216,9
Power ConsumptionkW5,265,75
Max. IntensityA11,812,7
Fixed 1ModelZP67KCE-TFD-522ZP144KCE-TFD-522
Quantity11
CapacitykW16,235,4
Power ConsumptionkW5,210,8
Max. IntensityA10,621,1
Fixed 2ModelZP67KCE-TFD-420
Quantity1
CapacitykW16,2
Power ConsumptionkW5,2
Max. IntensityA11,8
FanQuantity12
Flowm³/h12.00024.000
PowerkW0,6700.865 x 2
Sound Pressure (3)dB6567
Water Heat ExchangerTypeDouble TubeShell and Tube
Load LosskPa6015
VolumeL1042
Nominal Flowm³/h5,211,2
Max. Design Pressure Mpa11
Connection TypeFlangedFlanged
Hydraulic ConnectionsmmDN40 (1 1/2)DN 100 (4)
DimensionsNet (W x H x D)mm1514 x 1865 x 8412000 x 1880 x 900
Gross (W x H x D)mm1590 x 2065 x 9952090 x 2020 x 985
WeightNetKg380600
GrossKg400670
RefrigerantTypeR410AR410A
QuantityKg714
Electrical Connections (4)Power Wiringmm24 x 16 + T (L<20m)4 x 25 + T (L<20m)
Signal Wiringmm23 x 0.75 (Shielded)3 x 0.75 (Shielded)
Operating Ambient TemperatureRefrigerationºC10 to 4610 to 46
HeatingºC-10 to 21-10 to 21
Operating Water Temperature (5)RefrigerationºC5 to 175 to 17
HeatingºC40 to 5040 to 50

Note:

(1) Nominal cooling conditions: Water temperature 12ºC (Inlet), 7ºC (Outlet), Outdoor temperature 35ºC DB. Water flow 0.172 m3/(h·KW).

(2) Nominal heating conditions: Water temperature 40ºC (Inlet), 45ºC (Outlet), Outdoor temperature 7ºC DB and 6ºC WB. Water flow 0.172 m3/(h·KW).

(3) Noise level measured at a distance of 1m.

(4) Recommended power wiring for L < 20m, for longer distances it must be calculated.

(5) For the 65 kW model, it is possible to adjust the water temperature in cooling from 0 to 17ºC and in heating from 22 to 50ºC. (Refer to the technical manual)

Characteristics

  • Copeland Digital Scroll Compressor
  • Modular system
  • Easy connection
  • Safeguard function
  • New heat exchangers
  • Verification function
  • Silent operation
  • Built-in wired remote control
  • Hydronic kit not included

Technical documentation

Technical Data Sheet EN
User and Installation Manual (MUEN-30-HG) EN EN
User and Installation Manual (MUEN-65-HG) EN EN
Technical Manual EN