Heat Pump for DHW, Heating and Cooling Production MUNDOCLIMA Aerotherm Series
MUNDOCLIMA Aerotherm is an energy solution for home comfort that uses air as its main energy source. It is a flexible and cost-effective alternative to boilers and also allows the possibility of generating air conditioning.
High Performance with a COP of up to 4.45
With a COP of up to 4.45, MUNDOCLIMA Aerotherm supplies more heat with less energy consumption.
DHW, heating and cooling production
The MUNDOCLIMA Aerotherm heat pump not only allows use as heating but also allows the supply of domestic hot water (DHW) and on the other hand can also provide cooling (air conditioning), if combined with a fancoil or other system.
Split System with R410a Refrigerant
The Aerotherm system consists of an outdoor unit and an indoor unit, these are joined by R410a refrigerant gas pipe. The maximum pipe length between the outdoor and indoor unit is 30 m.
Indoor Unit with Hydraulic Module
The indoor unit incorporates the essential hydraulic components in each installation, such as a circulation pump, flow switch, expansion vessel, tank with electrical resistors, plate heat exchanger and water pressure gauge.
Intelligent control panel
The indoor unit also incorporates an intelligent control panel, which allows you to adjust all the operating parameters of the system in a simple and understandable way. In addition, there is the possibility of installing the control panel inside the house separately from the indoor unit.
Built-in ambient temperature sensor
The system incorporates an ambient temperature sensor to control the temperature of the room only through the control panel of the equipment and without the need to place an external thermostat.
DC Inverter compressor and fans
All outdoor units incorporate a DC Inverter compressor and fan motor, this improves the performance of the system at medium frequencies and ensures more sensitive and effective control.
Characteristics
- High performance with a COP of up to 4.45
- DHW, heating and cooling production
- Split system with R410a refrigerant
- Indoor unit with hydraulic module
- Intelligent control panel
- Built-in ambient temperature sensor
- DC Inverter compressor and fans
- Best value for money on the market
Technical Documentation
| Technical Data Sheet | ||
| Technical Catalog | ||
| User and Installation Manual | ||
| Control Panel User Manual | ||
| Technical Manual | ||
| Performance Table |
TECHNICAL SPECIFICATIONS
INDOOR UNIT:
| Model | AEROTHERM 8 KW | AEROTHERM 12 KW | AEROTHERM 16 KW | AEROTHERM 16 KW (400V) | |
|---|---|---|---|---|---|
| Code | SO30141 | SO30145 | SO30149 | SO30153 | |
| Nominal voltage | 230V-1-50Hz | 230V-1-50Hz | 230V-1-50Hz | 400V-3-50Hz | |
| Nominal power | 6,200 W (with resistors) | ||||
| Water temp. | Heat (fan coil) | 25 – 55ºC | 25 – 55ºC | 25 – 55ºC | 25 – 55ºC |
| Heat (underfloor) | 25 – 45ºC | 25 – 45ºC | 25 – 45ºC | 25 – 45ºC | |
| Cold (fan coil) | 7 – 25ºC | 7 – 25ºC | 7 – 25ºC | 7 – 25ºC | |
| Cold (underfloor) | 18 – 25ºC | 18 – 25ºC | 18 – 25ºC | 18 – 25ºC | |
| Support Resist. | 3 + 3 kW | 3 + 3 kW | 3 + 3 kW | 6 kW | |
| Dimensions | 900 x 500 x 324 mm | ||||
| Net weight | 57 kg | 57 kg | 57 kg | 60 kg | |
OUTDOOR UNIT:
| Model | AEROTHERM 8 KW | AEROTHERM 12 KW | AEROTHERM 16 KW | AEROTHERM 16 KW (400V) | ||
|---|---|---|---|---|---|---|
| Code | SO30140 | SO30144 | SO30148 | SO30152 | ||
| Nominal voltage | 230V-1-50Hz | 230V-1-50Hz | 230V-1-50Hz | 400V-3-50Hz | ||
| Capacity (1) | Heating | kW | 8,5 | 12,5 | 15,5 | 15,5 |
| Refrigeration | kW | 8,5 | 12,5 | 14,5 | 15 | |
| Consumption (1) | Heating | kW | 2,05 | 2,81 | 3,78 | 3,78 |
| Refrigeration | kW | 2,54 | 3,57 | 4,53 | 4,11 | |
| COP/EER (1) | W/W | 4,1 / 3,35 | 4,45 / 3,5 | 4,1 / 3,2 | 4,1 / 3,65 | |
| Capacity (2) | Heating | kW | 7,5 | 11 | 14 | 14 |
| Refrigeration | kW | 6,2 | 9,5 | 10,5 | 11 | |
| Consumption (2) | Heating | kW | 2,5 | 3,14 | 4 | 4,12 |
| Refrigeration | kW | 2,38 | 3,39 | 3,96 | 3,73 | |
| COP/EER (2) | W/W | 3 / 2,61 | 3,5 / 2,8 | 3,5 / 2,65 | 3,4 / 2,95 | |
| Compressor | BLDC Inverter | |||||
| Refrigerant charge | kg | 2,1 | 3,2 | 3,2 | 3,4 | |
| Refrig. connections | Gas | inch. | 5/8″ | 5/8″ | 5/8″ | 5/8″ |
| Liquid | inch. | 3/8″ | 3/8″ | 3/8″ | 3/8″ | |
| DHW Temp. | ºC | 40 – 80 (1″ M connection) | ||||
| Sound level | Heating | dB(A) | 55 | 57 | 58 | 58 |
| Refrigeration | dB(A) | 54 | 55 | 57 | 57 | |
| Dimensions | WxDxH | mm | 980 x 360 x 790 | 900 x 412 x 1345 | 900 x 412 x 1345 | 900 x 412 x 1345 |
| Net weight | kg | 75 | 106 | 106 | 107 | |
Notes:
(1) Capacity and powers based on the following conditions:
Refrigeration: Int. Water temp.: 23ºC/18ºC. Outdoor Temp.: 35ºC DB/24ºC WB.
Heating: Int. Water temp.: 30/35ºC. Ext. Air Temp.: 7ºC DB/6ºC WB.
(2) Capacity and powers based on the following conditions:
Refrigeration: Int. Water temp.: 12ºC/7ºC. Outdoor Temp.: 35ºC DB/24ºC WB.
Heating: Int. Water temp.: 40/45ºC. Ext. Air Temp.: 7ºC DB/6ºC WB.