MUCR-H5 Series Duct Type Split
TECHNICAL SPECIFICATIONS
| Model | MUCR-18-H5 | MUCR-24-H5 | ||
|---|---|---|---|---|
| Code | CL 20 781 | CL 20 782 | ||
| Cooling capacity (min-max) | kW | 5,3 (0,9-7,4) | 7,1 (1,2-9,9) | |
| Heating capacity (min-max) | kW | 5,6 (0,9-7.4) | 7,8 (1,2-10,9) | |
| Pdiseñonh (-10°C) | kW | 5,3 | 7,0 | |
| SEER | W/W | 6,1 | 6,1 | |
| SCOP | W/W | 4,0 | 4,0 | |
| Energy label | Refrigeration | A++ | A++ | |
| Heating | A+ | A+ | ||
| Electrical supply | V-Hz-F | 230-50-1 | 230-50-1 | |
| Indoor Unit | ||||
| Air flow (High/Medium/Low) | m3 /h | 1.000/900/750 | 1.480/1.300/1.090 | |
| Static pressure | Standard (Pa) | 25 | 25 | |
| Range (Pa) | 0~100 | 0~100 | ||
| Sound pressure level (High/Medium/Low) | dB(A) | 44/40/37 | 46/42/38 | |
| Dimensions (W x H x D) | mm | 920 x 270 x 635 | 920 x 270 x 635 | |
| Net weight | kg | 26,9 | 28 | |
| Outdoor Unit | ||||
| Air flow (High) | m3 /h | 2.200 | 2.700 | |
| Sound pressure level (High) | dB(A) | 53 | 63 | |
| Dimensions (W x H x D) | mm | 810 x 558 x 310 | 845 x 700 x 320 | |
| Net weight | kg | 36,7 | 48 | |
| Refrigerant piping (inches) | Liquid | 1/4″ | 3/8″ | |
| Gas | 1/2″ | 5/8″ | ||
| Refrigerant charge R410a | kg | 1,83 | 1,95 | |
Warning:
1. Data and specifications are subject to change without notice.
2. The sound level values correspond to the values obtained in the anechoic chamber.
PRE-INSTALLATION REQUIREMENTS
| MODEL | PIPING | ELECTRICAL CONNECTIONS | |||||||
|---|---|---|---|---|---|---|---|---|---|
| Gas | Liquid | Maximum length (B) | Maximum height difference (A) | Precharge up to | Additional charge | Power supply | Com. (C) | ||
| Indoor (E) | Outdoor (D) | ||||||||
| MUCR-18-H5 | 1/2″ | 1/4″ | 30 m | 20 m | 5 m | 15 gr/m | 2 x 1.5 + T | 2 x 2.5 + T | 2 x 0,75 (Shielded) |
| MUCR-24-H5 | 5/8″ | 3/8″ | 30 m | 20 m | 5 m | 30 gr/m | 2 x 1.5 + T | 2 x 2.5 + T | 2 x 0,75 (Shielded) |
Note:
The wall remote control connection cable (F) is supplied with the unit (5 wires).