MUCHR-H6 Series

Models 20 to 26

Models 40 and 45

TECHNICAL SPECIFICATIONS

ModelMUCHR-20-H6MUCHR-22-H6MUCHR-26-H6MUCHR-40-H6MUCHR-45-H6
CodeCL23904CL23905CL23906CL23912CL23913
Cooling (1)CapacitykW19,6622,5325,9538,9643,95
kcal/h16.91019.37822.32033.50937.801
ConsumptionkW6,907,608,4014,6016,30
EERkW/kW2,852,963,092,672,70
Heating (2)CapacitykW19,8622,1825,7841,3545,38
kcal/h17.08219.07722.17435.56539.031
ConsumptionkW6,906,708,4013,8015,40
COPkW/kW2,883,313,073,002,95
Indoor UnitMVD- Model200T1/DHN1-B250T1/DHN1-B280T1/DHN1-BD400T1/N1-FD450T1/N1-F
CodeCL23381CL23382CL23383CL23187CL23188
Electrical PowerF, V, Hz1N-, 220-240V, 50Hz
Nominal IntensityA66612,512,5
Flow Rate (High / Medium / Low)m3/h4820 / 4660 / 46204820 / 4660 / 46204820 / 4660 / 46207474 / 6072 / 49957474 / 6072 / 4995
Static Pressure Disp.Pa62 (40 200)62 (40 200)62 (40 200)200 (50 280)200 (50 280)
Sound Pressure (High / Medium / Low) (3)dB(A)57 / 53 / 5057 / 53 / 5057 / 53 / 5061 / 59 / 5661 / 59 / 56
Dimensions (W x H x D)mm1450 x 505 x 9251450 x 505 x 9251450 x 505 x 9251970 x 668 x 902.51970 x 668 x 902.5
Weightkg108108108232232
Drain Connectionmm3232323232
Power Cable (5)mm22 x 2.5 + T2 x 2.5 + T2 x 2.5 + T2 x 4 + T2 x 4 + T
Outdoor UnitMVD- ModelV200W/DRN1V224W/DRN1V260W/DRN1V400W/DRN1V450W/DRN1
CodeCL23269CL23270CL23271CL23272CL23273
Electrical PowerF, V, Hz3N-, 400V, 50Hz
Nominal IntensityA14,5016,2018,7033,0044,00
Flowm3/h10.99910.49410.49416.57516.575
Static Pressure Disp.Pa00000
Sound Pressure (4)dB(A)5959606262
Dimensions (W x H x D)mm1120 x 1558 x 4141120 x 1558 x 4141120 x 1558 x 4141360 x 1650 x 5401460 x 1650 x 540
WeightKg137147147240275
Power Cable (5)mm24 x 6 + T4 x 6 + T4 x 10 + T4 x 25 + T4 x 35 + T
RefrigerantTypeR410A
Pre-charged amountkg4,86,26,29,012,0
Additional charge (from 0 m)kg/m0,0570,0570,0570,1100,110
Refrigerant ConnectionsLiquid Linemm (in.)9.52 (3/8″)9.52 (3/8″)9.52 (3/8″)12.7 (1/2″)12.7 (1/2″)
Gas Linemm (in.)19.1 (3/4″)22.2 (7/8″)22.2 (7/8″)28.6 (1 1/8″)28.6 (1 1/8″)
Refrigerant Distances (6)Max. Vertical m2525252525
Totalm606060100100
Communication Cablemm23 x 0.75 (Shielded)
Remote controlModelKJR-29B
TypeWiring
Operating Temp. Range RefrigerationºC-15 to 43-15 to 43-15 to 43-5 to 43-5 to 43
HeatingºC-15 to 24-15 to 24-15 to 24-15 to 24-15 to 24

Notes:

(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for an equivalent pipe length of 8 m and height difference of 0 m.

(3) Sound pressure measured in an anechoic chamber at a distance of 1m from the front and 1.4m in height.

(4) Sound pressure measured in an anechoic chamber at a distance of 1m from the front and 1.2m in height (1.3m for models 20 to 26).

(5) Recommended power wiring for L 20m, for longer distances it must be calculated.

(6) Refrigerant distances when the outdoor unit is installed lower than the indoor units. Otherwise, instead of 30m it is 20m.

The design and specifications are subject to change without notice for product improvement.

Attention:

– Before start-up, the entire micro-switch S6 must be set to the OFF position on the outdoor unit.

– Models 40 and 45 do not include an air filter.

Characteristics

  • Front discharge outdoor unit
  • DC Inverter Compressor
  • Precise temperature control
  • High static pressure
  • Wall remote control and “Follow Me” function KJR-29B included
  • Wall remote control with weekly programmer KJR-120C (optional)
  • CCM centralized control (optional)

Technical documentation

Technical Data Sheet ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
User manual ES 18X18 EN 18X18
Installation manual. Indoor Unit up to 26 ES 18X18 EN 18X18
Installation Manual. Indoor Unit 40 and 45 ES 18X18 EN 18X18
Installation Manual. Outdoor Unit up to 26 ES 18X18 EN 18X18
Installation Manual. Outdoor Unit 40 to 45 EN EN