High-capacity Duct-Type Split Inverter MUCHR-H7 Series
TECHNICAL SPECIFICATIONS
| Model | MUCHR-75-H7T | MUCHR-96-H7T | ||||
|---|---|---|---|---|---|---|
| Code | CL21532 | CL21533 | ||||
| Cooling (*1) | Nominal capacity | kW | 22,4 | 28,0 | ||
| Nominal consumption | kW | 7,2 | 9,0 | |||
| EER | 3,11 | 3,11 | ||||
| Seasonal energy efficiency for space cooling | W/W | 189,6 | 187,8 | |||
| Heating (*2) | Nominal capacity | kW | 24,5 | 31,5 | ||
| Nominal consumption | W | 6,6 | 8,5 | |||
| COP | W/W | 3,17 | 3,71 | |||
| Seasonal energy efficiency for space heating | 137,7 | 136,2 | ||||
| Indoor Unit | Air flow (High / Medium / Low) | m3/h | 4.075 / 3.900 / 3.880 | 4.075 / 3.900 / 3.880 | ||
| Static Pressure | Nominal | Pa | 50 | 50 | ||
| Configurable (*3) | Pa | 0 ~ 150 | 0 ~ 150 | |||
| Sound pressure (High / Medium / Low) | dB(A) | 52 / 51 / 49 | 52 / 51 / 49 | |||
| Drain connection | mm | Ø32 | Ø32 | |||
| Electrical supply | V-Hz-F | 220-240V~ 50Hz, 1F | 220-240V~ 50Hz, 1F | |||
| Indoor power cable | mm2 | 2 x 2.5 + T | 2 x 2.5 + T | |||
| Wired remote control | KJR-29B | KJR-29B | ||||
| Supplied cable length (4 wires) | m | 6 | 6 | |||
| Dimensions (Width x Height x Depth) | mm | 1470 x 512 x 775 | 1470 x 512 x 775 | |||
| Weight | kg | 83 | 83 | |||
| Outdoor Unit | Air flow (High) | m3/h | 9.800 | 9.800 | ||
| Sound pressure (High) | dB(A) | 58 | 59 | |||
| Compressor (Brand / Model) | MITSUBISHI / LNB53FCAMC | |||||
| Electrical supply | V-Hz-F | 380-415V~ 50Hz, 3F | 380-415V~ 50Hz, 3F | |||
| Outdoor power cable | mm2 | 4 x 6 + T | 4 x 6 + T | |||
| Dimensions (Width x Height x Depth) | mm | 1120 x 1558 x 414 | 1120 x 1558 x 414 | |||
| Weight | kg | 148 | 148 | |||
| Set | Communication cable | mm2 | 3 x 0.75 (shielded) | |||
| Refrigerant | Type/GWP | R410A / 2088 | R410A / 2088 | |||
| Load | kg | 7,2 / 15,03 | 7,2 / 15,03 | |||
| Precharge up to | m | 5 | 5 | |||
| Additional charge (from 5m) | g/m | 30 | 30 | |||
| Design pressure | MPa | 4,4 / 2,6 | 4,4 / 2,6 | |||
| Refrigerant pipes | Liquid/Gas | inch | Ø9.52 / Ø25.1 (3/8″ / 1) | |||
| Maximum length (*4) | m | 50 | 50 | |||
| Maximum height difference | Higher OD | m | 25 | 25 | ||
| Lower OD | m | 30 | 30 | |||
| Operating temperature | Indoor (Cooling / Heating) | ºC | 17 ~ 32 / 0 ~ 30 | 17 ~ 32 / 0 ~ 30 | ||
| Outdoor (Cooling / Heating) | ºC | -15 ~ 43 / -15 ~ 24 | -15 ~ 43 / -15 ~ 24 | |||
Notes:
(*1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, 24ºC WB, for an equivalent pipe length of 7.5 m and height difference of 0 m.
(*2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, 6ºC WB, for an equivalent pipe length of 7.5 m and height difference of 0 m.
(*3) Pressure configurable via the ENC2 micro-switch on the electronic board of the indoor unit.
(*4) Minimum pipe length of 2 meters.
* The design and specifications are subject to change without notice for product improvement.
** The sound level values correspond to values obtained in an anechoic chamber