MUC-W7 Series

Universal Fan Coil – Horizontal / Vertical MUC-W7 Series

TECHNICAL SPECIFICATIONS

Model MUC-W7/SE-CE0711161924
Codewithout Enclosure (SE Version)CL04580CL04581CL04582CL04583CL04584
with Enclosure (CE Version)CL04590CL04591CL04592CL04593CL04594
RefrigerationCapacity (High / Medium / Low) (*1)kW2,07 / 1,52 / 1,073,25 / 2,63 / 2,124,57 / 3,35 / 2,625,43 / 4,32 / 3,587,17 / 5,67 / 4,72
Water flow (High / Medium / Low)m3/h0,36 / 0,27 / 0,200,59 / 0,49 / 0,380,81 / 0,60 / 0,470,93 / 0,78 / 0,631,29 / 0,99 / 0,84
Pressure drop (High / Medium / Low)kPa11,13 / 6,7 / 3,823,2 / 16,38 / 11,1425,52 / 15,03 / 9,9518,54 / 13,01 / 8,7130,94 / 18,96 / 14,04
Heating45ºCCapacity (High / Medium / Low) (*2)kW2,39 / 1,76 / 1,33,62 / 2,82 / 2,174,66 / 3,38 / 2,576,38 / 4,81 / 3,938,45 / 6,32 / 5,05
Water flow (High / Medium / Low)m3/h0,42 / 0,32 / 0,240,64 / 0,51 / 0,390,83 / 0,60 / 0,471,10 / 0,87 / 0,711,47 / 1,13 / 0,90
Pressure drop (High / Medium / Low)kPa8,9 / 7,29 / 4,319,57 / 15,1 / 9,821,58 / 12,5 / 7,9117,62 / 15,39 / 10,727,39 / 21,6 / 14,12
50ºCCapacity (High / Medium / Low) (*3)kW2,78 / 2,07 / 1,424,37 / 3,34 / 2,635,52 / 3,98 / 3,037,44 / 5,69 / 4,719,96 / 7,48 / 5,94
Water flow (High / Medium / Low)m3/h0,36 / 0,27 / 0,200,59 / 0,49 / 0,380,81 / 0,60 / 0,470,93 / 0,78 / 0,631,29 / 0,99 / 0,84
Pressure drop (High / Medium / Low)kPa11,99 / 5,22 / 322,9 / 13,86 / 9,123,02 / 12,41 / 7,724,16 / 12,51 / 8,534,9 / 16,71 / 12,38
Air flow (High / Medium / Low)m3/h369 / 272 / 196604 / 448 / 343678 / 492 / 3831.017 / 720 / 5881.509 / 1054 / 806
SE VersionPa1212121212
CE VersionPa00000
Heat exchanger water volumeL0,1950,2590,3440,4710,471
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
ConsumptionW15302636103
Sound pressure (*4)dB(A)39 / 31 / 2244 / 37 / 3140 / 32 / 2542 / 33 / 2851 / 42 / 35
Max. operating pressureMPa1,61,61,61,61,6
Max. inlet water temperatureºC6565656565
Water connectionsinch3/4″3/4″3/4″3/4″3/4″
Drain connectionmm1616161616
DimensionsSE Version (Width x Height x Depth) (*5)mm550 x 545 x 212750 x 545 x 212950 x 545 x 2121,250 x 545 x 2121,250 x 545 x 212
CE Version (Width x Height x Depth)mm800 x 592 x 2201,000 x 592 x 2121,200 x 592 x 2201,500 x 592 x 2201,500 x 592 x 220
WeightSE Versionkg1923,5273434
CE Versionkg24,434,234,24040

Notes:

(1) Cooling capacity for each of the 3 airflows and according to conditions: Inlet/outlet water temp 7/12°C, Ambient temp 27°C DB, 19°C WB.

(2) Heating capacity for each of the 3 airflows and according to conditions: Inlet/outlet water temp 45/40°C, Ambient temp 20°C.

(3) Heating capacity for each of the 3 airflows and according to conditions: Inlet/outlet water temp 50°C/*, Ambient temp 20°C.

(4) Sound pressure level measured in a semi-anechoic chamber.

(5) Does not include the dimensions of the electrical box (+50mm) and the valve tray (+86mm).

– The design and specifications are subject to change without notice for product improvement.

Characteristics

  • 2-pipe universal fan coil unit
  • Installation on floor or ceiling (vertical / horizontal)
  • Low consumption and silent DC fan motor
  • Front air inlet (CE version)
  • No need to use support feet (CE version)
  • Includes L-shaped condensate tray for the valve
  • Hydraulic connections on the left side (front view)

Technical documentation

Technical Data Sheet ES 18X18 EN 18X18 FR 18X18 FROM 18X18 PT 18X18
User and Installation Manual ES 18X18 EN 18X18
Technical Manual EN 18X18